Class A adjustable differential relay
Class A adjustable differential relay
Class A adjustable differential relay
Class A adjustable differential relay
Class A adjustable differential relay
Class A adjustable differential relay
Class A adjustable differential relay
Class A adjustable differential relay

Superimmunized Class A adjustable differential relay

€129.20 Tax included

€106.78 tax excl.

Adjustable electronic relay adjustable for industrial protection. Adjustable sensitivity between 0.03A and 3A and firing time between 0.02s and 1s, to be connected to an external toroidal transformer of the TD series. It has a switched contact for the firing element.

Superimmunized class "A".

Manufacturer's reference: RDER

Representative image for illustrative purposes, the item supplied will correspond to the indicated specifications.

No queries yet, leave the first!
 

Differential relay for industrial protection,with separate sensing transformer. Intended to ensure the protection of people and electrical installations against indirect contacts, both in single-phase and three-phase systems. The differential relay must be associated with a TD series toroidal sensing transformer.

Adjustable sensitivity between 0.03 and 0.3A and shooting time between 0.02 and 1s. DIN rail mounting and 230Vac supply voltage. Switched NA/NC output contact to trigger an external trigger element.

Class A differential protection immunized, for the detection of alternating and alternating leakage current with continuous component, which makes it especially recommended for electrical installations with the presence of currents distorted by the presence of harmonics.

Note: The measurement element, toroidal transformer is not included in the supply.

Technical details:

  • Manufacturer/Supplier: LS
  • Manufacturer's reference: RDE030
  • Type: Class A, superimmunized, high frequency current filtering
  • Sensitivity (I'n): adjustable between 0.03A and 3A
    • 0.03-0.1-0.3-0.5-1-2-3 A
  • Delay: adjustable between 0.02s and 1 second
  • Output contact: 1 switched contact NA/NC 10A. 250Vac
  • Maximum power: 2500VA
  • Electrical performance: 100x103 operations, 6A. 85oC with resistive load 250Vac
  • Relay power supply: 230Vac (± 20%) 50/60Hz 4VA
  • Type of reconnection: manual via Reset button or power outage
  • Operating temperature: -10o to 50oC
  • Fixing: via DIN rail
  • Dimensions: 35x85x73mm (2 modules)
  • Degree of protection: IP20 / IP41 transframe
  • Standards: IEC 61008-1, IEC 755, IEC 255-5

Led status indications:

  • Leakage LED on permanently: relay triggered
  • Power LED flashing and leaking on: transformer continuity failure detection
  • Leakage LED flashing: Indicates lower value leakage than selected
    • 1 flash every 2 sec.: 25%... 50% of the leakage current
    • 1 flash every 1 sec.: 50%... 75% of the leakage current
    • 2 flashes every 1s.: 75%... (
    • Permanent: 100%

Dimensions:

Dimensiones relé diferencial RDER

Mounting:

Conexionado relé diferencial RDER bobina emisión

Esquema conexionado relé diferencial bobina mínima

Material for professional use, install in compliance with the regulations in force at the installation site.

Questions

Be the first to ask a question about this product!

Question about the product

* Required fields
(read)

Responsible: ADAJUSA (CONSTRUCCIONES PBR, S.L.), purpose: Respond to requests for information, legitimacy: consent of the interested party, recipients: data will not be communicated to third parties, rights: Access, rectify and delete data, as well as other rights, as explained in the additional information. (read)

16 other products in the same category:

Customers who bought this product also bought: